Sma CLUSTER CONTROLLER Uživatelský manuál

Procházejte online nebo si stáhněte Uživatelský manuál pro Zařízení Sma CLUSTER CONTROLLER. SMA CLUSTER CONTROLLER User Manual Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 118
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků

Shrnutí obsahu

Strany 1 - SMACLUSTERCONTROLLER

UserManualSMACLUSTERCONTROLLERClusterController-BA-en-14 | Version 1.4AMERICAN ENGLISH

Strany 2 - Legal Provisions

17.2 Making the Proxy Configuration... 9117.3 Making the DHCP Configuration...

Strany 3

18.2 Errors in the ClusterController or the ConnectedDevicesGeneral informationProblem Cause and corrective measureThe ClusterController does not st

Strany 4 - Important Safety Instructions

Problem Cause and corrective measureAn incorrect total number of con-nected inverters is shown on the userinterface or the display.Communication with

Strany 5 - General Warnings

Problem Cause and corrective measureNo measured values for the con-nected temperature sensor are shownon the display.The temperature sensor is not cor

Strany 6

Problem Cause and corrective measureThe login page does not open. The ClusterController is not connected to the voltage sup-ply.Corrective measures:•

Strany 7

Problem Cause and corrective measureThe login page does not open. There is a problem in the LAN.Corrective measures:• Ensure that the network cables a

Strany 8

Events and Device StatusProblem Cause and corrective measureIn the event log, the wrench symbol( ) is displayed next to the eventtype.This event can o

Strany 9

CommunicationProblem Cause and corrective measureCommunication with at least one de-vice is disturbed.There may be a disturbance in the device.Correct

Strany 10 - Table of Contents

USB and UpdateProblem Cause and corrective measureThe update via the USB data carrierdoes not start.There are no update files on the USB data carrier

Strany 11 - 1.4 Symbols

Problem Cause and corrective measureNo inverters or not all inverters reportback with the version number of thesent update file.Due to missing DC inpu

Strany 12 - 1.6 Nomenclature

External FTP ServerProblem Cause and corrective measureThe ClusterController does notsend any data to the external FTPserver.An error has occurred in

Strany 13 - 2 Safety

1 Information on this Document1.1 ValidityThis document is valid for the SMAClusterController (models "CLCON-10" and "CLCON-S-10"

Strany 14 - 2.4 System Requirements

ModbusProblem Cause and corrective measureThe ClusterController cannot be ac-cessed by the Modbus client.The required Modbus server is not activated.

Strany 15 - 3 Product Description

SunnyPortalProblem Cause and corrective measureThe registration of the ClusterCon-troller in SunnyPortal failed.SunnyPortal cannot currently be ac

Strany 16

Problem Cause and corrective measureThe ClusterController does not sendany data to SunnyPortal.The data transmission is incorrectly configured.Corre

Strany 17

18.4 Resetting the ClusterControllerYou can reset the ClusterController via the keypad.Procedure:1. Call up the display view Settings. To do this, s

Strany 18

19 AccessoriesYou will find the accessories for your product in the following overview. If required, these can beordered from SMA or your distributor.

Strany 19

20 Compliance InformationFCC ComplianceThis device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions:1. This de

Strany 20 - 3.1.2 Type Label

21 ContactIf you have technical problems with our products, please contact the SMAServiceLine. We needthe following information in order to provide

Strany 21 - 3.1.3 LEDs

DanmarkDeutschlandÖsterreichSchweizSMA Solar Technology AGNiestetalSMA Online Service Center:www.SMA.de/ServiceSunny Boy, Sunny Mini Central,SunnyTri

Strany 22 - 3.1.4 Display

SMA Solar Technologywww.SMA-Solar.com

Strany 23 - 3.1.5 Keypad

Symbol ExplanationDesired resultA problem that might occur1.5 TypographiesTypography Use Examplebold• Display texts• Elements on a user interface• Ter

Strany 24 - 3.2 SunnyPortal

2 Safety2.1 Intended UseThe ClusterController is a device for monitoring and controlling SMAinverters with Speedwire/Webconnect interfaces in decent

Strany 25

2.3 Operating InformationHigh costs possible due to inappropriate Internet tariffsDepending on use, the data volume of the ClusterController transfer

Strany 26 - 4.2.1 Structure

3 Product Description3.1 ClusterController3.1.1 FunctionsThe ClusterController is a device for monitoring and controlling SMAinverters with Speedwi

Strany 27 - 4.2.2 Toolbar

Reading out, provision and administration of PV system dataThe ClusterController is the central communication unit for the system and continuously re

Strany 28 - 4.2.3 System Tree

Implementation and feedback of setpoints for active power limitation when PVelectricity is directly marketedThe PV current generated by your system ca

Strany 29 - 4.2.4 Device Menu

Performing Updates for the ClusterController and the InvertersYou have the option of performing updates for the ClusterController and the inverters

Strany 30 - 4.2.4.4 Updates Menu

Position DesignationI Ripple control receiver or remote terminal unitK SubstationL Control roomM Grid control roomN Utility gridFigure 3: Decentralize

Strany 31 - Status of the update file

Legal ProvisionsThe information contained in these documents is property of SMA Solar Technology AG. Anypublication, whether in whole or in part, requ

Strany 32

Position DesignationE Irradiation sensorF ClusterControllerG Industrial loadH SunnyPortalI RouterK Ripple control receiver or remote terminal unitL

Strany 33

Symbol Designation ExplanationCE marking The product complies with the require-ments of the applicable EU directives.WEEE designation Do not dispose o

Strany 34 - 4.2.4.6 Events Menu

Figure 4: Network port LEDsPosition Designation Color ExplanationA Link/activity LED Green Shows the status and the activity of the networkconnection

Strany 35 - 4.2.4.7 Update and Save Menu

Display view ExplanationSystem overview Displays the system status, the current daily yield, the nominal sys-tem power and the current setpoints for a

Strany 36

Designation Explanation[OK]Confirms the selected action[ESC]Cancels the selected actionⓘOpens the display view System status3.2 SunnyPortalSunnyPort

Strany 37 - 4.2.5 Symbols

4 User Interface of the ClusterController4.1 User Groups and User RightsThe ClusterController distinguishes between the user groups User and Install

Strany 38

4.2 Overview of the User Interface4.2.1 StructureABCDEFigure 6: User interface of the ClusterController (example)Position Designation ExplanationA To

Strany 39

Position Designation ExplanationD Content area Displays the content of the selected menuE Status bar Displays the following information:• Serial numbe

Strany 40 - 6 System Settings

4.2.3 System TreeIn the system tree, all devices in a system are represented in a tree structure. The system tree isdivided into the hierarchy levels,

Strany 41 - 6.5 Setting the Time Format

Symbol Designation ExplanationErrorAt least one device in the system has the status Fault.There is a problem with this device that could not be elimi-

Strany 42 - 6.7 Settings for System Time

Legal ProvisionsCopyright © 2015 SMA America,LLC. All rights reserved.No part of this document may be reproduced, stored in a retrieval system, or tr

Strany 43

4.2.4.2 Instantaneous Values MenuInstantaneous values are measured or calculated values for the device, such as temperature andpower. Different inform

Strany 44 - 7 Device Configuration

Update status ExplanationUpdate available The update file is ready for sending to the devices in the sys-tem.Update in process The update process is r

Strany 45

Parameter ExplanationStart setpoint active power limita-tionLower limit for the setpoint for the active power limitation re-lated to the inverter para

Strany 46 - ClusterController

Example of the importance of lower and upper limits for setpoints4mA is set as the initial value for the active power limitation setpoint and 16mA i

Strany 47

Parameter ExplanationMax. change in case of powerincreaseIndicates the maximum change in percentage points per timeinterval that occurs once an active

Strany 48 - 8 Exporting System Data

Severity of the EventSymbol ExplanationThis event can only be rectified by a user with Installer rights (see Section9.1,page55).This event can only

Strany 49 - 8.2.2 XML Format

Symbol Designation ExplanationGrid monitoring Information that affects the utility grid and is par-tially protected by the personalSMAGridGuard code

Strany 50 - File structure (example)

4.2.5 SymbolsSymbols for access rightsSymbol Designation ExplanationPadlock symbol Not possible to access the deviceThe device password does not match

Strany 51

Symbol Designation ExplanationStopwatch Indicates that a value is from more than ten minutesagoCalendar function Opens a calendar for selecting a date

Strany 52

5 Logging Into or Out of the ClusterControllerLogging Into the ClusterController1. If the IP address of the ClusterController is unknown, read off

Strany 53 - Server (FTP Push)

Important Safety InstructionsSAVE THESE INSTRUCTIONSThis manual contains important instructions for the following products:• SMAClusterControllerThi

Strany 54

6 System Settings6.1 Display Settings6.1.1 Setting the Display LanguageAvailable display languagesThe display languages of the ClusterController are

Strany 55 - 9 System Monitoring

6.3 Setting the Date FormatNo effect on data exportsThe changes to the format only affect the display on the user interface and theClusterController

Strany 56

4. In the drop-down list Time format, select the desired time format.Abbreviation ExplanationHH 24-hour formathh 12-hour formatmm Minutesss Seconds5.

Strany 57 - Version of the Devices

Procedure:1. Select the ClusterController in the system tree and select the menu Settings in the devicemenu.2. Select the parameter group Device >

Strany 58

7 Device Configuration7.1 Setting the Characteristic Curve of the IrradiationSensorIf you have connected an irradiation sensor to the ClusterControll

Strany 59 - 10.5 Adding an Inverter

4. Set the desired parameters.5. Select [Save].☑ The settings are saved in the ClusterController and are then transmitted to all devices of theaffect

Strany 60 - 11 SunnyPortal

4. In the drop-down list Activated, select the entry No.5. Select [Save].☑ The settings are saved in the ClusterController and are then transmitted t

Strany 61 - 11 Sunny Portal

4. Select the desired configuration file and select [Open].☑ The file name of the selected configuration file is displayed in the field Restore device

Strany 62

8 Exporting System Data8.1 Export OptionsThe instantaneous values and the parameters of the devices in the system can be saved, displayedand prepared

Strany 63

Line Explanation2 Empty line3 Name of device (serial number or changed devicename)4 Device type5 Serial number of the device6 Name of the values7 Type

Strany 64 - 12 Modbus Configuration

General WarningsAll electrical installations must be made in accordance with the local and National ElectricalCode® ANSI/NFPA 70 or the Canadian Elect

Strany 65

File structure (example)Designation ExplanationInfo InformationCreated Date of creationCulture LanguageUtcOffset Offset in minutes to UTCDST Daylight

Strany 66 - 13 Grid Management Services

Designation ExplanationPeriod Length of the measurement interval in secondsTimeStamp Time stamp at which the average was calculated8.3 Setting the Mea

Strany 67

Procedure:• Connect the USB data carrier to the ClusterController at USB port 1.☑ Depending on the available storage capacity of the USB data carrier

Strany 68

Procedure:1. The IP address of the ClusterController, the user ID and the system password are to beentered in the address bar of the web browser as f

Strany 69

8. In the field Server path, enter the subdirectory to which the ClusterController is to save thedata on the external FTP server.9. In the field Serv

Strany 70

9 System Monitoring9.1 Displaying EventsYou can have an event log displayed for each device in the system. All events for the device arelogged in the

Strany 71

• Select [Edit].• In the field Activated, select the entry Yes.• If the e-mail is to be displayed in a language other than the currently configuredlan

Strany 72 - Power in %"

10 System Management and Replacing Components10.1 Changing System Names or Device Names1. Select the ClusterController in the system tree and select

Strany 73

3. To read off the firmware version of the integrated communication interface (e.g. SMASpeedwire/Webconnect data module), select the parameter group T

Strany 74

10.5 Adding an Inverter1. Connect the new inverter to the ClusterController (see the ClusterController installationmanual).2. Log into the ClusterC

Strany 75

Table of Contents1 Information on this Document ... 111.1 Validity...

Strany 76

11 SunnyPortal11.1 Registering the ClusterController in SunnyPortalNo combination of ClusterController and SunnyWebBox in one SunnyPortalsystemI

Strany 77 - 14 Update

11.2 Setting Data Transmission to SunnyPortalRequirement:☐ You must already be registered in SunnyPortal (see Section11.1, page60).Procedure:1. Se

Strany 78

5. Select [Save].6. Adjust the strictness of communication monitoring in SunnyPortal if required (see the usermanual of the ClusterController in Sun

Strany 79 - 14.2 Manual Update

11.6 Adjusting the System Identifier for SunnyPortalIn the following cases, you must adjust the system identifier for SunnyPortal in theClusterCont

Strany 80

12 Modbus Configuration12.1 Activating the Modbus ServerWhen using a Modbus client, you must activate the required Modbus server via the user interfac

Strany 81

• Select the desired SMA Modbus profile and select [Open].☑ The file name of the SMA Modbus profile is displayed in the field Update SMAModbus profile

Strany 82

13 Grid Management Services13.1 Options for Implementing Grid Management ServiceSetpointsYou can have the ClusterController implement the grid manage

Strany 83

13.2 Setting Parameters for Grid Management Services inthe InvertersTo enable the inverters in the system to implement the grid management service set

Strany 84 - Password

13.3 Settings for Active Power Limitation13.3.1 Controlling Active Power LimitationInput signals up to 21mA possibleFor an analog signal source, the

Strany 85 - 15.4.1 Requesting a PUK

• In the field Final value input signal, enter the desired value.• In the field Start setpoint active power limitation, enter the desired value.• In t

Strany 86

4.2.4.6 Events Menu... 344.2.4.7 Update and Save Menu ...

Strany 87

To regulate active power feed-in at the grid-connection point, perform the following actions in thespecified order. The exact procedure is described i

Strany 88 - Access via WAN IP Address

6. In the drop-down list Source for system active power select the measurement source usedat the grid-connection point. If you are using an EnergyMet

Strany 89 - Access via DynDNS

7. In the field Active power enter the desired value for the fixed active power limitation.8. Make the settings for the fallback (see Section13.5, pa

Strany 90 - 17 Network Configuration

• Select the group Settings of analog inputs.• In the field Failure tolerance time, enter the desired time interval.• In the field Initial value input

Strany 91

• In the drop-down list Signal source, select the desired signal source. Note that thedesired Modbus server must be activated in the ClusterControlle

Strany 92 - 17.5 Changing the NAT Port

longer be up to date. This prevents potential yield loss. The fallback must be activated andconfigured via the user interface of the ClusterControlle

Strany 93 - 5. Select [Save]

Requirement:☐ The inverters in the system must be equipped with the latest inverter firmware version (seeproduct page of the inverter at www.SMA-Solar

Strany 94

14 Update14.1 Automatic Update (Recommended)14.1.1 Setting the Automatic Update for ClusterControllerIn the automatic update of the ClusterControlle

Strany 95

Do not change the update source during the automatic update processIf the update source is changed during the automatic update process, the update pro

Strany 96

14.2 Manual Update14.2.1 Carrying Out a Manual Update for ClusterControllerYou can always perform a manual update, even if the automatic update is ac

Strany 97

8.5 Exporting System Data to the Integrated FTP Server ... 528.5.1 Setting the Export Format for System Data...

Strany 98

• Connect the USB data carrier to the computer.• In the first partition of the USB data carrier, create a file folder in the root directory withthe ti

Strany 99 - 18.1.2 Network Port LEDs

3. In the area Available updates, highlight the desired update file and select [Download].☑ The ClusterController downloads the update file from the

Strany 100 - User Interface and Display

• In the system tree, select the system and select the menu Updates in the device menu.• Select the desired device type, e.g. SB5000TL-21.• In the ar

Strany 101 - 18 Troubleshooting

15 Passwords and SMAGridGuard15.1 Requirements for a Secure System PasswordFrom the perspective of system communication, all devices with the same p

Strany 102

15.3 Adapting the Device Password to the SystemPasswordIf the password of a device is different from the system password, the device will be displayed

Strany 103

• In the field Set installer password, enter the previous system password for the usergroup Installer.• In the field Confirm password, confirm the sys

Strany 104

Procedure:1. Reset the password settings of the ClusterController via the display:• Select the display view Settings. To do this, simultaneously pres

Strany 105 - Events and Device Status

15.5 Setting SMAGridGuard ModeWhen the inverters are delivered, the SMAGridGuard parameters have a default settingdepending on the country. Change

Strany 106 - Communication

16 Setting Up Access via the InternetIf the ClusterController is integrated in a LAN with a router, you can also access the user interfaceof the Clus

Strany 107 - USB and Update

Access via DynDNS1. Set up the desired Internet address with a DynDNS service, e.g. at dyndns.com.2. Set up the router for DynDNS (see router manual).

Strany 108 - EnergyMeter

13 Grid Management Services ... 6613.1 Options for Implementing Grid Management Service Setpoints...

Strany 109 - External FTP Server

17 Network Configuration17.1 Configuration for Static LAN17.1.1 Configuring the ClusterController for Static LANDifferent IP address ranges required

Strany 110

• In the drop-down list Activated, select the entry No.8. In the group Ethernet, make the desired settings for the static LAN and select [Save].☑ The

Strany 111 - SunnyPortal

3. Select the parameter group External communication > Proxy settings and make thedesired proxy configuration. Tip: The proxy settings for the web

Strany 112

3. Select [Edit].4. In the field Port, enter the desired port (default setting: port 80).5. Select [Save].17 Network ConfigurationSMASolarTechnology

Strany 113

18 Troubleshooting18.1 LED States18.1.1 Operation LEDsAssignment of the Status LED ( ):The status LED can display the following statuses:• Status of t

Strany 114 - 19 Accessories

LED Status Cause and corrective measureStatus ( )glowing green Normal operationglowing yellowAt least one device has the status Warning.Corrective mea

Strany 115 - 20 Compliance Information

LED Status Cause and corrective measureStatus ( )flashing yellow An update of the ClusterController or the con-nected devices is currently taking pla

Strany 116 - 21 Contact

LED Status Cause and corrective measureStatus ( )glowing red The SD memory card in the ClusterController maybe defective.Corrective measures:• Check

Strany 117 - 9:;*<+%,='3)>+%

LED Status Cause and corrective measureData carrier status ()off The ClusterController is starting and no informa-tion is yet available for data expo

Strany 118 - SMA Solar Technology

18.1.2 Network Port LEDsLED Status Cause and corrective measureLink/activity(green)off No network connection established.The ClusterController is not